Additional requirements for Current Transformers

Views : 665
Update time : 2024-08-08 09:53:17
3.4.215  
knee point voltage 
r.m.s. value of the sinusoidal voltage at rated frequency applied to the secondary terminals  of the transformer, all other terminals being open-circuited, which, when increased by 10 %, causes the r.m.s. value of the exciting current to increase by 50 % 
[SOURCE: IEC 60050-321:1986, 321-02-34]  
3.4.216   
knee point e.m.f. 
e.m.f. of a current transformer at rated frequency, which, when increased by 10 %, causes the r.m.s. value of the exciting current to increase by 50 % 
Note 1 to entry: While the knee point voltage can be applied to the secondary terminals of a current transformer, the knee point e.m.f. is not directly accessible. The values of  the knee point voltage and  of the knee point e.m.f. are deemed as equal, due to the minor influence of the voltage drop across the secondary winding resistance. 
3.4.217  
rated knee point e.m.f. 
lower limit of the knee point e.m.f.  
Note 1 to entry: The rated knee point e.m.f. appears in the specifications of class PX and PXR protective current transformers.
3.4.218  
rated turns ratio 
specified ratio of the number of primary turns to the number of secondary turns  
EXAMPLE 1   1/600  (meaning 1 primary turn to 600 secondary turns) 
EXAMPLE 2   2/1200 (meaning 2 primary turns to 1200 secondary turns)  
Note 1 to entry: The rated turns ratio appears in the specifications of class PX and PXR protective current transformers. 
Note 2 to entry: Rated turns ratio and rated transformation ratio are both defined as primary to secondary entities. 
If they shall be compared, the value of the rated turns ratio has to be inverted. 
3.4.219  
turns ratio error 
difference between the actual turns ratio and the rated turns ratio, expressed as a percentage of the rated turns ratio 
3.4.220  
dimensioning factor 
factor to indicate the multiple of rated secondary current (Isr) occurring under power system fault conditions, inclusive of safety margins, up to which the transformer is required to meet performance requirements 
Note 1 to entry: See formula under 3.4.217. 
3.4.221  
instantaneous error current 
difference between the instantaneous values of the secondary current multiplied by the rated transformation ratio and the primary current
Note 1 to entry: When both alternating current components and direct current components are present, the constituent components are separately identified as follows
3.4.222  
peak instantaneous error 
peak value of instantaneous error current (see 3.4.221) for the specified duty cycle, expressed as a percentage of the peak value of the rated primary short-circuit current
3.4.223  
peak alternating error component 
peak value of the alternating component of the instantaneous error current, expressed as a percentage of the peak value of the rated primary short-circuit current
3.4.224  
specified duty cycle (C-O and / or C-O-C-O) 
duty cycle in which, during each specified energization, the primary short circuit current is assumed to have the worst-case inception angle (see Figure 201) 
3.4.225  
Specified primary time constant 
that specified value of the time constant of the d.c. component of the primary short-circuit current on which the transient performance of the current transformer is based (see Figure 202) 
3.4.226  
duration of the first fault 
duration of the fault in a C-O duty cycle, or of the first fault in a C-O-C-O duty cycle 
Note 1 to entry: See Figure 201. 
3.4.227  
duration of the second fault 
duration of the second fault in a C-O-C-O duty cycle 
Note 1 to entry: See Figure 201. 
3.4.228  
specified time to accuracy limit in the first fault 
time in a C-O duty cycle, or in the first energization of a C-O-C-O duty cycle, during which the specified accuracy has to be maintained 
Note 1 to entry: See Figure 201. This time interval is usually defined by the critical measuring time of the associated protection scheme.  
3.4.229  
specified time to accuracy limit in the second fault 
time in the second energization of a C-O-C-O duty cycle during which the specified accuracy has to be maintained 
Note 1 to entry: See Figure 201. This time interval is usually defined by the critical measuring time of the associated protection scheme.  
Related News
Read More >>
Where Is the HK-58 Current Transformer Used in Malaysian LV Projects? Where Is the HK-58 Current Transformer Used in Malaysian LV Projects?
Sep .28.2026
HK-58 current transformer is designed for Malaysian LV switchboards, busbar panels and energy monitoring upgrades, enabling easier current measurement in factories and commercial buildings without major wiring changes.
Together Under the Same Moon: Celebrating Mid-Autumn Festival with Our Team Together Under the Same Moon: Celebrating Mid-Autumn Festival with Our Team
Sep .24.2026
HEYI celebrates the Mid-Autumn Festival by preparing thoughtful gifts for employees, expressing appreciation for their dedication, teamwork, and contribution while highlighting a warm and people-centered company culture.
Where Is the LMK5-100 Current Transformer Used in Australian Electrical Projects? Where Is the LMK5-100 Current Transformer Used in Australian Electrical Projects?
Sep .18.2026
Explore where the LMK5-100 current transformer is used in Australian switchboards, energy meters, busbar systems, factories, solar projects and infrastructure for accurate high-current energy monitoring.
Where Is a Current Transformer Used in South Africa’s LV Electrical Projects? Where Is a Current Transformer Used in South Africa’s LV Electrical Projects?
Sep .14.2026
Discover where a current transformer can be used in South Africa’s LV projects. Learn how DP-23 supports electrical panels, energy meters, motors, HVAC, and LV busbars with split-core installation, flexible ratios, and easy retrofit.