Additional requirements for Current Transformers

Views : 952
Update time : 2024-08-05 08:50:58
3.4.205  
instrument security factor 
ratio of rated instrument limit primary current to the rated primary current 
Note 1 to entry: Attention should be paid to the fact that the actual instrument security factor is affected by the burden. When the burden value is significantly lower than  rated one, larger current values will be produced on the secondary side in the case of short-circuit current. 
Note 2 to entry: In the event of system fault currents flowing through the primary winding of a current transformer, the safety of the apparatus supplied by the transformer is at its highest when the value of the rated instrument security factor (FS) is at its lowest. 
[SOURCE: IEC 60050-321:1986, 321-02-28, modified notes to entry]  
3.4.206  
secondary limiting e.m.f. for measuring current transformers 
product of the instrument security factor FS, the rated secondary current and the vectorial sum of the rated burden and the impedance of the secondary winding  
This method will give a higher value than the actual one. It was chosen in order to apply the same test method as 
used for protective current transformers. Refer to 7.2.6.202 and 7.2.6.203.  
[SOURCE: IEC 60050-321:1986, 321-02-31, modified title, synonym and note to entry]  
3.4.207  
rated accuracy limit primary current 
value of primary current up to which the current transformer will comply with the requirements for composite error 
[SOURCE: IEC 60050-321:1986, 321-02-29]  
3.4.208  
accuracy limit factor 
ratio of the rated accuracy limit primary current to the rated primary current  
[SOURCE: IEC 60050-321:1986, 321-02-30]  
3.4.209  
secondary limiting e.m.f. for protective current transformers 
product of the accuracy limit factor, the rated secondary current and the vectorial sum of the rated burden and the impedance of the secondary winding
3.4.210  
saturation flux 
maximum value of secondary linked flux in a current transformer, which corresponds to the magnetic saturation of the core material 
Note 1 to entry: The most suitable procedure for the determination of the saturation is given with the d.c. saturation method described in 2B.2.3. 
Note 2 to entry: In the former standard IEC 60044-6, it was defined as a knee point value, which characterized the transition from the non-saturated to the fully saturated state of a core. This definition could not gain acceptance because the saturation value was too low, and led to misunderstandings and contradictions. Therefore, it was replaced by it which defines the condition of complete saturation. 
3.4.211  
remanent flux   
value of secondary linked flux which would remain in the core 3 min after the interruption of a magnetizing current of sufficient magnitude to induce saturation flux
3.4.212  
remanence factor 
ratio of the remanent flux to the saturation flux, expressed as a percentage   
3.4.213  
secondary loop time constant 
value of the time constant of the secondary loop of the current transformer obtained from the sum of the magnetizing and the leakage inductances and the secondary loop resistance 
3.4.214  
excitation characteristic 
graphical or tabular presentation of the relationship between the r.m.s. value of the exciting current and a sinusoidal voltage applied to the secondary terminals of a current transformer, the primary and other windings being open-circuited, over a range of values sufficient to define the characteristics from low levels of excitation up to 1.1 times the knee point e.m.f. 
Related News
Read More >>
Outdoor Split-Core CT for Light Rail: HEYI’s Korean Railway Applications Outdoor Split-Core CT for Light Rail: HEYI’s Korean Railway Applications
Nov .20.2026
Explore how HEYI’s outdoor split-core CT supports AC feeder monitoring in Korean railway stations, outdoor cabinets and depots.
Where Can the HEYI CCT-24 CT Clamp Current Sensor Be Used? Where Can the HEYI CCT-24 CT Clamp Current Sensor Be Used?
Nov .19.2026
Explore HEYI CCT-24 for solar storage, building submetering, equipment monitoring and distributed power measurement.
A Beautiful Land, A Long-Term Vision for HEYI in Central Asia A Beautiful Land, A Long-Term Vision for HEYI in Central Asia
Nov .18.2026
Discover HEYI’s long-term vision for Central Asia and how HEYI current transformers, split-core CTs and electrical measurement solutions aim to build stronger recognition across the region.
HEYI Advances High-Accuracy Split-Core Current Transformers and Eastern European Cooperation HEYI Advances High-Accuracy Split-Core Current Transformers and Eastern European Cooperation
Nov .17.2026
HEYI advances Class 0.5S and Class 0.2 Split-Core CT designs for energy monitoring at low primary current ratios and explores technical cooperation in Eastern Europe.