Additional requirements for Current Transformers

Views : 775
Update time : 2024-08-12 15:16:43
3.4.230  
fault repetition time 
time interval between interruption and re-application of the primary short-circuit current during a circuit breaker auto-reclosing duty cycle in case of a non-successful fault clearance 
3.4.231  
secondary loop resistance 
total resistance of the secondary circuit 
3.4.232  
rated symmetrical short-circuit current factor 
ratio of the rated primary short circuit current to the rated primary current  
3.4.233  
transient factor 
ratio of the secondary linked flux at a specified point of time in a duty cycle to the peak value of its a.c. component
3.4.234  
transient dimensioning factor 
dimensioning factor to consider the increase of the secondary linked flux due to a d.c. component of the primary short circuit current 
3.4.235  
Low-leakage reactance current transformer 
current transformer for which measurements made at the secondary terminals (while primary open-circuited) are sufficient for an assessment of its protection performance up to the required accuracy limit  
3.4.236  
high-leakage reactance current transformer 
current transformer which does not satisfy the requirements of 3.4.235, and for which an additional allowance is made by the manufacturer to take account of influencing effects which result in additional leakage flux 
3.4.237  
rated equivalent limiting secondary e.m.f. 
that r.m.s. value of the equivalent secondary circuit e.m.f. at rated frequency necessary to meet the requirements of the specified duty cycle
3.4.238  
peak value of the exciting secondary current at Eal
peak value of the exciting current when a voltage corresponding to Eal is applied to the secondary terminals while the primary winding is open 
3.4.239  
factor of construction 
factor reflecting the possible differences in measuring results at limiting conditions between direct test and indirect test methods 
Note 1 to entry: The measuring procedure is given in  2B.3.3. 
5 Ratings 
5.3 Rated insulation levels 
5.3.2 Rated primary terminal insulation level 
Clause 5.3.2 of IEC 61869-1:2007  is applicable with the addition of the following: 
For a current transformer without primary winding and without primary insulation of its own, the value Um = 0,72 kV is assumed. 
5.3.5 Insulation requirements for secondary terminals 
Clause 5.3.5 of IEC 61869-1:2007  is applicable with the addition of the following: 
The secondary winding insulation of class PX and class PXR current transformers having a rated knee point shall be capable of withstanding a rated power frequency withstand voltage of 5 kV r.m.s. for 60 s. 
5.3.201 Inter-turn insulation requirements 
The rated withstand voltage for inter-turn insulation shall be 4,5 kV peak. 
For class PX and class PXR current transformers having a rated knee point e.m.f. of greater than 450 V, the rated withstand voltage for the inter-turn insulation shall be a peak voltage of 10 times the r.m.s. value of the specified knee point e.m.f., or 10 kV peak, whichever is the 
lower. 
NOTE 1 Due to the test procedure, the wave shape can be highly distorted. 
NOTE 2 In accordance with the test procedure 7.3.204, lower voltage values may result. 
Related News
Read More >>
Outdoor Split-Core CT for Light Rail: HEYI’s Korean Railway Applications Outdoor Split-Core CT for Light Rail: HEYI’s Korean Railway Applications
Nov .20.2026
Explore how HEYI’s outdoor split-core CT supports AC feeder monitoring in Korean railway stations, outdoor cabinets and depots.
Where Can the HEYI CCT-24 CT Clamp Current Sensor Be Used? Where Can the HEYI CCT-24 CT Clamp Current Sensor Be Used?
Nov .19.2026
Explore HEYI CCT-24 for solar storage, building submetering, equipment monitoring and distributed power measurement.
A Beautiful Land, A Long-Term Vision for HEYI in Central Asia A Beautiful Land, A Long-Term Vision for HEYI in Central Asia
Nov .18.2026
Discover HEYI’s long-term vision for Central Asia and how HEYI current transformers, split-core CTs and electrical measurement solutions aim to build stronger recognition across the region.
HEYI Advances High-Accuracy Split-Core Current Transformers and Eastern European Cooperation HEYI Advances High-Accuracy Split-Core Current Transformers and Eastern European Cooperation
Nov .17.2026
HEYI advances Class 0.5S and Class 0.2 Split-Core CT designs for energy monitoring at low primary current ratios and explores technical cooperation in Eastern Europe.