The HYCA-08-MD is a high-performance Residual Current Detection Module (RDC-MD) developed by Wenzhou Heyi Electrical Co., Ltd. Designed for earth leakage protection in electrical systems, this product complies with IEC 62752 and IEC 62955 standards while meeting RoHS/REACH environmental directives. With a theoretical design life exceeding 20 years, it serves as a critical safety component for electric vehicle charging stations and power conversion equipment.
RDC HYCA-08/MD Type B Residual Current Sensor

Key Features

  1. Power Characteristics

    • Single power supply: 4.85-5.15VDC (nominal 5V)

    • Low power design: <110mW

    • Power ripple requirement: ≤150mV

  2. Output Characteristics

    • Logic level output: Low level ≤0.6V, High level ≥4.2V

    • TRIP signal: Transitions from low to high when leakage current exceeds threshold

    • Status signal: Outputs 1kHz PWM waveform with 50% duty cycle during normal operation

  3. Environmental Robustness

    • Operating temperature range: -40℃ to +85℃

    • Storage temperature range: -20℃ to +65℃

    • Operational altitude: <4000m

    • Humidity tolerance: ≤95%RH

Technical Specifications

Residual Current Detection Characteristics

Waveform Type Frequency Min Trip Current(mA) Typ Trip Current(mA) Max Trip Current(mA)
S-DC - 3 4.5 6
2PDC - 3.5 5 7
3PDC - 3.1 4.5 6.2

Response Time Characteristics

For 6mA S-DC leakage current:

  • Typical response: 120ms

  • Maximum response: 1000ms

For 200mA high current scenarios:

  • All waveform types respond within 50-100ms

Typical Application Circuit

The module features PCB mounting with a standard application circuit including:

  • Power filtering

  • Core detection module

  • Signal conditioning

  • Control electronics interface

Pin definition:

  1. VDD: Power input (5V±5%)

  2. TRIP: Fault output signal

  3. GND: Power ground

  4. Status: Monitoring output

  5. TEST: Self-test input

Self-Test and Calibration Functions

HYCA-08-MD incorporates comprehensive self-test capabilities:

  1. Zero-drift Calibration: Grounding TEST pin triggers automatic zero-point calculation and calibration value storage

  2. Simulation Test: Generates internal 6.53mADC simulated leakage current for functional verification

  3. Timing Requirements:

    • Power ramp rate ≤5ms/V

    • Self-test command duration: 50-100ms

    • Calibration completion: ≈200ms

    • Total test cycle: ≈1.5s

Critical Note: Main circuit must be disconnected during self-test to prevent actual leakage current interference.

Application Fields

  1. EV Charging Systems
    Safety protection for public charging stations against insulation faults

  2. Power Conversion Equipment
    Leakage current monitoring for inverters and converters

  3. Smart Grid Systems
    Ground fault detection in power distribution networks

Design Advantages

  1. Dual-Threshold Design
    Trip threshold (IAT) at 100% of typical value, reset threshold (IAX) at 55% prevents signal oscillation

  2. Wide Detection Range
    Capable of detecting leakage currents from mA to A levels

  3. Power Monitoring
    Built-in supply voltage monitoring with automatic status output switching below 4.69V

  4. Environmental Durability
    Validated across -40℃ to +85℃ temperature range

Conclusion

The HYCA-08-MD Residual Current Monitoring Unit delivers high precision, reliability, and comprehensive self-protection for modern power electronic systems. Particularly in the rapidly evolving EV charging infrastructure, this product effectively prevents personal injury and equipment damage caused by insulation faults, making it an ideal choice that meets international safety standards.

Related News
Read More >>
Outdoor Split-Core CT for Light Rail: HEYI’s Korean Railway Applications Outdoor Split-Core CT for Light Rail: HEYI’s Korean Railway Applications
Nov .20.2026
Explore how HEYI’s outdoor split-core CT supports AC feeder monitoring in Korean railway stations, outdoor cabinets and depots.
Where Can the HEYI CCT-24 CT Clamp Current Sensor Be Used? Where Can the HEYI CCT-24 CT Clamp Current Sensor Be Used?
Nov .19.2026
Explore HEYI CCT-24 for solar storage, building submetering, equipment monitoring and distributed power measurement.
A Beautiful Land, A Long-Term Vision for HEYI in Central Asia A Beautiful Land, A Long-Term Vision for HEYI in Central Asia
Nov .18.2026
Discover HEYI’s long-term vision for Central Asia and how HEYI current transformers, split-core CTs and electrical measurement solutions aim to build stronger recognition across the region.
HEYI Advances High-Accuracy Split-Core Current Transformers and Eastern European Cooperation HEYI Advances High-Accuracy Split-Core Current Transformers and Eastern European Cooperation
Nov .17.2026
HEYI advances Class 0.5S and Class 0.2 Split-Core CT designs for energy monitoring at low primary current ratios and explores technical cooperation in Eastern Europe.