Protective current transformer classes for transient performance

Views : 1317
Update time : 2024-09-11 14:21:56
NOTE A larger variety of curves is given in the Technical Report IEC 61869-100 TR.  



2B.1.3 C-O-C-O duty cycles 

The transient dimensioning for auto-reclosure duty cycles has to be done separately for each cycle according to the equations given above. 

For cores having a high secondary time constant (typically TPX cores), there is no significant flux declination after t’. 

For cores having a low secondary time constant (typically TPY and TPZ cores), the secondary linked flux declines exponentially with the secondary time constant  Ts during the fault repetition time. In this case, no analytical formula exists for the time argument t in the term for the first cycle, and several case differentiations may be necessary.  

Fig. 2B.7 shows a typical case where saturation is reached after  t’al. The flux is limited to saturation flux before  t’ is reached. It declines to a value which is low enough to remain below saturation up to  t’’al. Ignoring saturation (shoved by curve, the declined flux starts from a higher level at the beginning of the second cycle. This example demonstrates the interdependency between the core dimensioning in the first and in the second cycle, and the determination of Ktd. 

NOTE 1 The formula for the C-O-C-O-cycle, which was given in the preceding standard IEC 60044-6, ignores saturation within the first cycle and leads in many cases to unnecessarily high Ktd values. See Fig. 2B.7. 

It is therefore recommended to draw a graph similar to the one in Fig. 2B.7, in order to make oneself familiar with the actual situation.
Related News
Read More >>
Outdoor Split-Core CT for Light Rail: HEYI’s Korean Railway Applications Outdoor Split-Core CT for Light Rail: HEYI’s Korean Railway Applications
Nov .20.2026
Explore how HEYI’s outdoor split-core CT supports AC feeder monitoring in Korean railway stations, outdoor cabinets and depots.
Where Can the HEYI CCT-24 CT Clamp Current Sensor Be Used? Where Can the HEYI CCT-24 CT Clamp Current Sensor Be Used?
Nov .19.2026
Explore HEYI CCT-24 for solar storage, building submetering, equipment monitoring and distributed power measurement.
A Beautiful Land, A Long-Term Vision for HEYI in Central Asia A Beautiful Land, A Long-Term Vision for HEYI in Central Asia
Nov .18.2026
Discover HEYI’s long-term vision for Central Asia and how HEYI current transformers, split-core CTs and electrical measurement solutions aim to build stronger recognition across the region.
HEYI Advances High-Accuracy Split-Core Current Transformers and Eastern European Cooperation HEYI Advances High-Accuracy Split-Core Current Transformers and Eastern European Cooperation
Nov .17.2026
HEYI advances Class 0.5S and Class 0.2 Split-Core CT designs for energy monitoring at low primary current ratios and explores technical cooperation in Eastern Europe.