Magnetic saturation margin

Views : 840
Update time : 2024-10-23 08:37:48
When the magnetic flux density of the current transformer core is 1.5 times the rated current and rated load, the error should not be greater than 1.5 times the error limit under the rated current and rated load.

[Article Interpretation] The selection of magnetic saturation margin is related to the instrument safety factor of the current transformer, because the current transformer for measurement has instrument safety factor requirements. When the primary current reaches the specified instrument safety current (rated primary current multiplied by the instrument safety factor), the error of the current transformer should not be greater than 10%, so as to protect the secondary instrument from damage caused by large current shock.

According to normal design, the instrument safety factor of the current transformer using cold-rolled silicon steel sheet core is about 10; the instrument safety factor of the current transformer using iron-nickel alloy core is about 3, but iron-nickel alloy is expensive and is only used in precision current transformers.

Therefore, the instrument safety factor of current transformer products in the past is not a problem that needs to be discussed.

In recent years, new and inexpensive soft magnetic materials, such as amorphous and ultra-fine crystal materials, have been widely used, and their magnetic permeability is several times higher than that of silicon steel sheets.

Higher magnetic flux density can be used to achieve the same accuracy.

In order to save core material and reduce volume, designers often take a relatively high rated magnetic flux density, which results in the instrument safety factor being reduced to less than 3.

On-site verification has found that the magnetic saturation point of some current transformer cores made of amorphous and ultra-microcrystalline materials is very close to the 120% point of the rated current, and a slight asymmetry of the magnetic circuit will exceed the tolerance.

Considering that during the error inspection and use of the current transformer, when the distance between the primary return conductor and the core is close to the geometric dimensions of the transformer body, the magnetic field generated by the large current conductor may cause the core magnetic flux density to have an asymmetry of 1/6.

If both parts of the asymmetric core are not saturated, the error of the current transformer will not be significantly affected.

However, if one side of the core is saturated, the error of the current transformer will change significantly, making the error of the transformer unqualified.

Therefore, it is necessary to ensure that the core has a certain magnetic saturation margin during design.

Since the maximum operating current of the current transformer is usually 1.2 times the rated current, it is more appropriate to increase it by 1.2 times on this basis and take 1.5 times.
Related News
Read More >>
Where Is the HK-58 Current Transformer Used in Malaysian LV Projects? Where Is the HK-58 Current Transformer Used in Malaysian LV Projects?
Sep .28.2026
HK-58 current transformer is designed for Malaysian LV switchboards, busbar panels and energy monitoring upgrades, enabling easier current measurement in factories and commercial buildings without major wiring changes.
Together Under the Same Moon: Celebrating Mid-Autumn Festival with Our Team Together Under the Same Moon: Celebrating Mid-Autumn Festival with Our Team
Sep .24.2026
HEYI celebrates the Mid-Autumn Festival by preparing thoughtful gifts for employees, expressing appreciation for their dedication, teamwork, and contribution while highlighting a warm and people-centered company culture.
Where Is the LMK5-100 Current Transformer Used in Australian Electrical Projects? Where Is the LMK5-100 Current Transformer Used in Australian Electrical Projects?
Sep .18.2026
Explore where the LMK5-100 current transformer is used in Australian switchboards, energy meters, busbar systems, factories, solar projects and infrastructure for accurate high-current energy monitoring.
Where Is a Current Transformer Used in South Africa’s LV Electrical Projects? Where Is a Current Transformer Used in South Africa’s LV Electrical Projects?
Sep .14.2026
Discover where a current transformer can be used in South Africa’s LV projects. Learn how DP-23 supports electrical panels, energy meters, motors, HVAC, and LV busbars with split-core installation, flexible ratios, and easy retrofit.