Lift variation, stability and general technical requirements

Views : 527
Update time : 2024-12-04 16:41:24
3.2 Rise and fall variation

JJG313-2010】The difference in the error measurement results of the same current percentage point during the current rise and fall of the current transformer is called the rise and fall variation.

For the current transformer with an accuracy level of 0.2 or above used as a standard, the rise and fall variation shall not be greater than 1/5 of its error limit.

JJG314-2010】The difference in the error measurement results of the same voltage percentage point during the voltage rise and fall of the voltage transformer is called the rise and fall variation.

For the voltage transformer with an accuracy level of 0.2 or above used as a standard, the rise and fall variation shall not be greater than 1/5 of its error limit.

3.3 Stability

JJG313-2010】The error change of the current transformer shall not be greater than 1/3 of its error limit during the calibration cycle.

JJG314-2010】The error change of the voltage transformer shall not be greater than 1/3 of its error limit during the calibration cycle.
【Article Interpretation】As a measuring instrument, the value must be stable. If the deviation occurs between two calibrations, it will cause a value error.

If the standard instrument being tested is used for value transfer, it will cause value confusion.

Therefore, the measuring instrument must show a sufficiently good value stability at least in the interval between two calibrations.

Generally speaking, the value stability of electromagnetic transformers is relatively good, but if an error compensation circuit is added to the secondary side of the transformer, or an iron core material with unstable magnetic properties is used, it will affect the value stability of the transformer.

When determining the value stability index of the measuring transformer, the actual situation in my country should also be considered.

When revising the JJG313-1994 and JJG314-1994 regulations, the value stability requirements of the measuring transformer were specifically proposed, which should at least reach the level of general instruments, that is, one-third of the error limit.

4 General technical requirements

4.1 Appearance

JJG313-2010】The appearance of the current transformer should be intact, the terminal markings should be clear and complete, and the insulation surface should be dry and free of discharge marks.

【JJG314-2010】The appearance of the voltage transformer should be intact, and the terminal markings should be clear and complete.

The oil level of the oil-insulated transformer is correct, the gas-insulated transformer has normal filling pressure, the high-voltage bushing has no insulation defects, and there are no discharge marks on the high and low voltage insulation surfaces.

4.2 Insulation

【JJG313-2010】

4.2.1 The insulation resistance of the current transformer shall comply with the requirements of JB/T5472 Section 6.7

4.2.2 The power frequency insulation withstand voltage of the current transformer shall comply with the requirements of JB/T5472 Section 6.8.1.

【JJG314-2010】

4.2.1 The insulation resistance shall comply with the requirements of JB/T5473 Section 6.6.

4.2.2 The power frequency insulation withstand voltage shall comply with the requirements of JB/T5473 Section 6.7.1

4.2.3 The power frequency induction withstand voltage shall comply with the requirements of JB/T 5473 Section 6.7.2
Related News
Read More >>
Current Transformer for Electrical Panels and Power Monitoring in Indonesia Current Transformer for Electrical Panels and Power Monitoring in Indonesia
Jun .17.2026
HEYI MSQ-30 current transformer supports energy meters, industrial power monitoring, low voltage panels, and power monitoring systems in Indonesia with stable current signals.
Current Transformer for Compact Switchgear and DIN Rail Power Monitoring in Russia Current Transformer for Compact Switchgear and DIN Rail Power Monitoring in Russia
Jun .10.2026
HEYI CP series current transformer is designed for compact switchgear, DIN rail current transformer installation, and power monitoring cabinet applications in Russia, offering flexible mounting and reliable low-voltage measurement support.
Current Transformer for Energy Metering and Industrial Power Monitoring in Colombia Current Transformer for Energy Metering and Industrial Power Monitoring in Colombia
Jun .08.2026
MSQ current transformer supports Colombian low voltage energy metering, industrial power monitoring, electrical cabinets, and distribution panels with stable signals, wide window design, and flexible current ratios.
Current Transformer for Retrofit Power Monitoring in Philippine Electrical Panelsc Current Transformer for Retrofit Power Monitoring in Philippine Electrical Panelsc
Jun .04.2026
DP split core current transformer for Philippine electrical panel retrofit, switchgear upgrade, generator load monitoring, and industrial power monitoring applications.