Alternative measurement of the ratio error

Views : 666
Update time : 2024-09-30 09:38:00
For low-leakage reactance current transformers, the following indirect test will lead to results which are very close to the results obtained in the direct test.  

Nevertheless, routine tests for ratio error determination shall always be performed as a direct test, as this method gives the highest evidence of the “low-leakage reactance property” of a core, including magnetic homogeneity of the iron core. On the other hand, the alternative method is suitable for on-site measurements, and for monitoring purposes. 

In this case, it shall be noted that this method never considers the influence of current flow in the neighborhood of the current transformer. 

For the determination of the ratio error, the simplified equivalent circuit diagram shown in Figure 2E.1 is used: 

A substantially sinusoidal voltage is applied to the secondary terminals S1 – S2 of the current transformer. The test voltage across the terminals  Us Test and the current  Is Test are measured. The injected voltage should generate an e.m.f. across the main inductivity with the same amplitude as during operation with a certain current and the actual burden. The e.m.f. can be calculated from the test results by subtracting the voltage drop across the winding resistance Rct from the test voltage Us Test across the S1 – S2 terminals. This subtraction has to be done in the complex plane. The measured current Is Test is equal the error current. 

The ratio error can be expressed as: 

with: 

the ratio error can be expressed as: 

To determine the ratio error for a certain secondary current  Is the following test procedure is proposed: 

Calculation of the secondary voltage across S1 – S2: 

Measurement of the secondary winding resistance R (value at the actual temperature) 

Calculation of the corresponding e.m.f.    

Injection of 

into the secondary terminals S1 – S2 

Measurement of the voltage Up Test across P1 - P2 

Calculation of the turns ratio  

Calculation of the corresponding Ip

The ratio error can be calculated as: 
Related News
Read More >>
Outdoor Split-Core CT for Light Rail: HEYI’s Korean Railway Applications Outdoor Split-Core CT for Light Rail: HEYI’s Korean Railway Applications
Nov .20.2026
Explore how HEYI’s outdoor split-core CT supports AC feeder monitoring in Korean railway stations, outdoor cabinets and depots.
Where Can the HEYI CCT-24 CT Clamp Current Sensor Be Used? Where Can the HEYI CCT-24 CT Clamp Current Sensor Be Used?
Nov .19.2026
Explore HEYI CCT-24 for solar storage, building submetering, equipment monitoring and distributed power measurement.
A Beautiful Land, A Long-Term Vision for HEYI in Central Asia A Beautiful Land, A Long-Term Vision for HEYI in Central Asia
Nov .18.2026
Discover HEYI’s long-term vision for Central Asia and how HEYI current transformers, split-core CTs and electrical measurement solutions aim to build stronger recognition across the region.
HEYI Advances High-Accuracy Split-Core Current Transformers and Eastern European Cooperation HEYI Advances High-Accuracy Split-Core Current Transformers and Eastern European Cooperation
Nov .17.2026
HEYI advances Class 0.5S and Class 0.2 Split-Core CT designs for energy monitoring at low primary current ratios and explores technical cooperation in Eastern Europe.