LZZB9-35Q transformer is epoxy resin cast strut totally enclosed structure.Apply the rated voltage of 35kV and below.The rated frequency 50Hz line current,energy measurment and relay.
| TRANSDUCER | |
| Rated insulation level | 40.5/95/185kV |
| Load power factor | 0.8(lag) |
| Surface creepage distance |
>875mm |
| Rated secondary current | 5A/1A |
| Product standard | GB1208 |
| Safety factor |
FS<10 |
Specification
| Rated primary current | Accuracy class | Rated output | Short-time thermal current | Rated Dynamic current | ||||
| 0.2,0.2S | 0.5,0.5S | 10P10 | 10P15 | 10P20 | ||||
| 30~100 | 0.2(S)/10P10/10P10,0.2(S) 10P15/10P15,0.2(S)/10P10/ 10P20,0.2(S)/10P15/10P20, 0.5/10P10/10P10,0.5/10P15 /10P15,0.5/10P10/10P20, 0.5/10P15/10P20 |
15 | 15 | 50 | 30 | 20 | 375Iln | 150Iln/3 |
| 150 | 31.5/1 | 80 | ||||||
| 200 | 31.5/2 | 80 | ||||||
| 300~500 | 15 | 15 | 50 | 30 | 20 | 31.5/3 | 80 | |
| 600~800 | 15 | 15 | 50 | 40 | 30 | 31.5/4 | 80 | |
| 1000~2000 | 40 | 50 | 50 | 50 | 30 | 14702 | 100 | |
Dimensions
| LZZB9-35Q | |||
![]() |
![]() |
![]() |
![]() |
Accuracy test



Tel:13968747975
E-mail: bethy@heyiele.com
Add:(Zhejiang Lierde Relay Co., Ltd.) Xinguang Ind. Zone, Liushi Town, Wenzhou, Zhejiang, ChinaYou can get a beautiful gift by interacting with us in the following ways
HEYI © All Rights Reserved.