Charging Pile Residual Current Sensors: Introducing HYCA-16
Charging pile residual current sensors, epitomized by HYCA-16, rely on advanced electromagnetic induction. Detecting current variations during leakage, the sensor ensures swift and accurate fault identification.
| Model | Corresponding standards | DC trigger threshold | AC trigger threshold |
| HYCA-16/PD | IEC62955 | 6mA | 30mA |
| Absolute maximum ratings (not operating) | ||||
| Electrical data | Symbol | Unit | Specification | Conditions |
| Load dump vervoltage | UC | V | 32 | 400ms |
| Over-voltage | UC | V | 25 | 1 minute |
| Reverse polarity | UC | V | -16 | 1 minute |
| Minimum supply voltage | UCmin | V | 6 | Continuous not operating |
| Maximum supply voltage | UCmax | V | 18 | Continuous not operating← |
| Creepage distance | dcp | mm | 7.2 | |
| Clearance | dci | mm | 6.9 | |
| RMS voltage for AC insulation test | Ud | KV | 2.5 | 50HZ, 1minute |
| Insulation resistance | Rins | MΩ | 500 | 500 V iso 16750-2 |
|
Electrical data – Ratings: |
||||
|
Action current |
Unit | Min. | Typ | Max. |
|
Operating current AC |
mA | 20 | 22.8 | 26 |
|
Operating current A0 |
mA | 11 | 15 | 30 |
|
Operating current A90 |
mA | 10 | 18 | 30 |
|
Operating current A135 |
mA |
10 | 24 | 35 |
|
Operating current 2PDC |
mA |
3.5 | 5 | 7 |
|
Operating current 3PDC |
mA |
3.1 | 4.6 | 6.2 |
|
Operating current S-DC |
mA | 3 | 4.6 | 6 |
|
Operating current F |
mA |
18 | 24 | 38 |
|
|
||||
|
Wav |
Fre.q | Unit | Current | Typ |
| AC | 50HZ | ms | 30mA | 60 |
|
AC |
50HZ |
ms | 60mA | 30 |
|
AC |
50HZ |
ms | 150mA | 15 |
| AC | 50HZ |
ms | 5A-100A | 15 |
| A0 | 50HZ |
ms | 42mA | 38 |
| A0 | 50HZ |
ms | 84mA | 30 |
| A0 | 50HZ |
ms | 210mA | 25 |
| A0 | 50HZ | ms | 42mA+6mADC | 38 |
| A0 | 50HZ |
ms | 84mA+6mADC | 30 |
| A0 | 50HZ |
ms | 210mA+6mADC | 25 |
| S-DC | - |
ms | 6mA | 120 |
| S-DC | - |
ms | 60mA | 25 |
| S-DC | - |
ms | 300mA | 25 |
| 2PDC/3PDC | 50HZ |
ms | 60mA | 25 |
| 2PDC/3PDC | 50HZ |
ms | 120mA | 20 |
| 2PDC/3PDC | 50HZ |
ms | 300mA | 20 |
| 2PDC/3PDC | 50HZ | ms | 5A-50A | 15 |
| F | - | ms | 210mA | 15 |
Dimensions
| Mechanical dimension(for reference only) |
![]() |
Standards
1. Does HYCA-16/PD support both AC and DC residual current detection?
The HYCA-16/PD technical table lists 6 mA DC and 30 mA AC trigger thresholds. Its protection behavior for different waveforms and current levels should be checked against the complete datasheet and the intended EV charger test plan.
2. How is HYCA-16/PD different from HYCA-16/MD?
HYCA-16/PD includes a listed AC threshold in addition to 6 mA DC, whereas HYCA-16/MD is presented as a DC monitoring variant. Confirm the required output behavior and system protection architecture before choosing between them.
3. Can HYCA-16/PD be used with a Mode 3 charging station?
The product page associates the HYCA-16 series with IEC 62955 and EV charging applications. Integration into a Mode 3 station requires confirmation of the residual-current functions, sensing arrangement, controller interface and external disconnecting device.
4. What response-time values should be checked for HYCA-16/PD?
The webpage lists typical response times for AC and DC fault-current conditions. A 6 mA DC value should not be treated as the total charger disconnection time. The complete device must be tested with its controller and switching components.