Residual current device sensor (RCDs) or residual current sensors are indispensable safety components used to protect against electrical and ground faults in a variety of applications. Their high sensitivity, fast tripping mechanisms and compatibility with a variety of electrical systems make them vital for ensuring electrical safety in residential and industrial environments and preventing accidents and damage.
Standards and Regulations:
Residual current device sensor are subject to various national and international standards and regulations that define their installation requirements and performance standards. HYCA-F03 complies with IEC62752, IEC62955, UL2231 standards.
| Model | Corresponding standards | DC trigger threshold | AC trigger threshold |
| HYCA-03/MD | IEC62752 | 6mA | - |
| Electrical/Reliability Characteristics | |
| Working Temperature | -40℃~85℃ |
| Storage Temparature | -20℃~65℃ |
| Supply Voltage(VDD) | 4.85~5.15 VDC recommend 4.9-5.1 VDC |
| Static Power Consumption | 110mW |
| Clearance (Primary-Primary/Secondary) |
≥6.5mm ≥10mm |
| Creepage Primary-Primary/Secondary) |
≥8mm ≥10mm |
| Voltage Input, low level | 0~0.6VDC |
| Voltage Input, high level | 4.2~5VDC |
| Designed Life | ≥20 years |
| Working Altitude | ≤4000m |
| Trip-Current (residual current related characteristics. | |||||
| Wav. | Freq. | Min. | Typ | Max. | Unit |
| AC | 50Hz | 20.0 | 23.0 | 26.0 | mA |
| A0° | 50Hz | 11.0 | 15.0 | 30.0 | mA |
| A90° | 50Hz | 10.0 | 20.0 | 30.0 | mA |
| A135° | 50Hz | 10.0 | 24.0 | 35.0 | mA |
| 2PDC | 50Hz | 3.5 | 5.0 | 7.0 | mA |
| 3PDC | 50Hz | 3.1 | 4.6 | 6.2 | mA |
| S-DC | – | 3.0 | 4.6 | 6.0 | mA |
| Trip-Time (residual current related characteristics | ||||
| Wav. | Freq. | Current | TYP. | Unit |
| AC | 50Hz | 30mA | 25 | ms |
| AC | 50Hz | 60mA | 16 | ms |
| AC | 50Hz | 150mA | 15 | ms |
| AC | 50Hz | 5A~100A | 8.5 | ms |
| A0° | 50Hz | 42mA | 25 | ms |
| A0° | 50Hz | 84mA | 18 | ms |
| A0° | 50Hz | 210mA | 10 | ms |
| A0° | 50Hz | 42mA+6mADC | 18 | ms |
| A0° | 50Hz | 84mA+6mADC | 15 | ms |
| A0° | 50Hz | 210mA+6mADC | 15 | ms |
| S-DC | 6mA | 48 | ms | |
| S-DC | 60mA | 16 | ms | |
| S-DC | 300mA | 8.5 | ms | |
| 2PDC/3PDC | 50Hz | 60mA | 20 | ms |
| 2PDC/3PDC | 50Hz | 120mA | 25 | ms |
| 2PDC/3PDC | 50Hz | 300mA | 12 | ms |
| 2PDC/3PDC | 50Hz | 5~50A | 12 | ms |
Dimensions
| Mechanical dimension(for reference only) |
![]() |
Standards
IEC62752
IEC62955
UL2231
1. Does HYCA-03/MD provide 6 mA DC residual current monitoring?
HYCA-03/MD is identified as a 6 mA DC residual current monitoring variant for EV charging. The published model summary does not assign it a 30 mA AC protective threshold. Specify the separate AC residual-current protection used in your charging system.
2. What is the difference between HYCA-03/MD and HYCA-03/PD?
The model tables distinguish HYCA-03/MD as a DC monitoring configuration, while HYCA-03/PD lists 6 mA DC and 30 mA AC thresholds. Select the version according to the charger protection architecture and verify the output interface and response characteristics in the correct datasheet.
3. Can HYCA-03/MD replace a complete residual current protective device?
Do not treat the monitoring sensor as a complete RCD or protective switch. The charger needs an appropriate protective arrangement, including any required AC residual-current protection and disconnection hardware, validated as a complete system under the applicable standard.
4. What information is needed to integrate HYCA-03/MD into a control board?
Provide the supply voltage, required monitoring output, fault-response logic, conductor arrangement, maximum charging current and available mounting area. The current HYCA-03/MD wiring diagram should be checked before the PCB and protection circuit are finalized.
5. How should an OEM verify 6 mA DC monitoring with HYCA-03/MD?
Use a controlled residual-current test setup and the relevant standard test waveforms. Check the sensor output at specified smooth and pulsating DC values, then verify that the charger controller and switching arrangement provide the required system response.